Thermokon · Room controller · Modbus
Fan coil room thermostat with a large display and five buttons, for 2 pipe and 4 pipe units, with Modbus RTU.
Availability and lead time confirmed on your quote
Part number703314
The LCF02 controls fan coil units and modulating valves (PWM or 0 to 10 V), in 2 pipe or 4 pipe systems. It has five buttons, a 64 x 41 mm backlit display and a flush-mounted housing for a standard 60 mm EU box. Three output arrangements are on the price list: five relays, two 0 to 10 V outputs with three relays, or three 0 to 10 V outputs with two relays, so you can drive an EC fan or a six-way valve. Two inputs take occupancy, window, dew point or change-over contacts, and there is an input for a remote NTC10k. RS485 Modbus RTU lets a supervisor override the control parameters. Supply is 24 V.
From the manufacturer's datasheet for LCF02 RS485 Modbus.