Kieback&Peter · Local override module
TMU-PO is a cabinet door touch module for local hand override of analog and binary signals, used with the BMD1204-PO or BMA0804-PO.
Availability and lead time confirmed on your quote
Part numberTMU-PO
From the manufacturer's datasheet for TMU-PO.
The TMU-PO is the operating module of the Kieback&Peter local override and indication system (LVB). It mounts in a round cut-out in the cabinet door and has two 2.4 inch colour displays (240 x 320 pixels) with touch operation and an energy-saving dimmer. It connects point to point over the LO and ID bus to a BMD1204-PO or BMA0804-PO input/output module and lets an operator override the connected analog and binary signals by hand. The backbone connection (200 m) links it to a TMC-PO central module that locks and releases operation. It is powered through the bus, IP54 on the front, and has no switches or potentiometers. TMB-PO dummy covers fill empty slots; Z851 and ADRA070-PO adapter plates and frames hold up to four modules.