The input/output module with 64 binary inputs or outputs. It receives DDC4000 binary signals in the automation system and activates binary control functions. Contacts are Volt Free and the first 8 can be used for Meter Pulse Reading to a limit of 80Hz. The binary outputs are transistor based and are switching the 0v of the external 24vDC supply out to any external interface relays.