Thermokon · Duct sensor
Duct or immersion temperature sensor with a passive element, in probe lengths from 50 to 450 mm.
Availability and lead time confirmed on your quote
Part number621045
From the manufacturer's datasheet for AKF10+ passive.
The AKF10+ passive measures air temperature in ducts and, with a thermowell pocket, liquid temperature as an immersion sensor. The output is the resistance of the chosen element, so it connects to any controller input of that type. Elements on the price list are Pt100, Pt1000, Pt1000 1/3 DIN, NTC10k, Ni1000, Ni1000TK5000 and LM235Z, each with a 6 mm stainless steel probe. Duct mounting needs an MF6DS or MF6 flange; immersion use needs a THVADS or THMSDS pocket.