Loading the page
Thermokon · Pressure sensor
Differential pressure transmitter for liquids in four ranges from 0 to 1 bar up to 0 to 6 bar, with a 0 to 10 V or 4 to 20 mA output.
Availability and lead time confirmed on your quote
Part number346702
From the manufacturer's datasheet for DPL active.
The DPL measures differential pressure in liquids. Typical uses are supply and return flows in HVAC and process systems, and monitoring filters and compressors. It has a stainless steel G1/4 connection and a ceramic measuring cell, and connects through a DIN 43650 type A angle plug. A 5 m cable with a pre-fitted connector is available as an accessory. The range is chosen by part (1, 2.5, 4 or 6 bar) and the output by suffix: V for voltage, A for current.