Logicboks · Optimiser compensator · BACnet
SYX661 is a compact heating optimiser compensator for NTC10 sensors, with versions to replace Trend, Honeywell AQ2000, Satchwell CSC and Drayton Theta II controllers.
Availability and lead time confirmed on your quote
Part numberSYX661-CSC-V-T
From the manufacturer's datasheet for SYX661.
The SYX661 is an optimiser compensator controller for simple heating circuits, designed around NTC10 temperature sensors. It controls a single compensated heating zone through a mixing valve or boiler modulation, with a heating time schedule, pump control with optional room sensor influence, and a hot water output. It is available as a direct replacement for Trend controllers and in versions for Honeywell AQ2000, Satchwell CSC (with or without time clock) and Drayton Theta II controllers, all using NTC10 sensors. The controller has a backlit text display with set knob and buttons, plus a built-in web server so settings, time schedules and overrides can be changed from a browser. Functions include optimum start and stop, day economy, three-stage frost protection, pump run-on, up to two boilers with lead rotation, valve and pump exercise, a 30 minute service mode, four heating periods per day and Auto, Summer, Continuous, Frost and Service overrides. Alarm messages are logged with the event time. It mounts on a DIN rail and runs from a 110 to 230 V AC supply. A TPC35 or TPC56 remote colour touch panel (as SYX-TPC35 or SYX-TPC56) or a TPC070 (SYX-TPC070) can be added, and mounting brackets and a wall box are listed separately.