Thermokon · Power thyristor
Three-phase power thyristor controller for loads up to 78 kW at 400 V AC, such as heating coils, fans, pumps and industrial ovens.
Availability and lead time confirmed on your quote
Part number260190
From the manufacturer's datasheet for TS2 three-phase active.
The TS2 three-phase is a thyristor power controller for ohmic and inductive loads such as fans, pumps, lamps, heating coils and industrial ovens. It switches without wear and with a high efficiency. It is available for 75 A (50 kW), 90 A (60 kW) and 120 A (78 kW) at 400 V AC, each in a standard and an SP version. The setpoint comes from 0 to 10 V, 0 to 20 mA or 4 to 20 mA, or from a 2.5 to 10 kohm potentiometer, and a PTC input is also provided. Nine LEDs show the state of the device, and two floating changeover contacts report 100% output and fault.